Figure Reference Guide

Navigation Menu

Operators Manual

Doc #PI0259 Rev 1.0 ?

Table of Contents

<#comment>

Figure Reference Guide

Part Numbers

DS012-LOW-VOLTAGELV Bridge System: includes one each SFI-HV801-01 and SFI-HV802-01
SFI-LV801-01Low Voltage Bridge Control Interface
SFI-LV802-01Low Voltage Bridge Equipment Interface
SFI-LV803-01Low Voltage Bridge Expansion Equipment Interface

Overview

The Sure-Fi Low Voltage Bridge System consists of two Interface units:

Control Interface

Control Interface

Equipment Interface

Equipment Interface

The Sure-Fi DS012-LOW-VOLTAGE Bridge System includes two interface units: The Control Interface, and the Equipment Interface. The system is factory paired and is ready for use immediately without any configuration required. The system provides a wireless connection (bridge) between the two units for up to eight relays.

<#comment>

The Thermostat Interface connects to the Thermostat and is mounted behind the Thermostat or within the wall and communicates the Thermostat’s output states wirelessly to the Equipment Interface, located at and wired to the HVAC Equipment. The Equipment Interface presents the output states from the Thermostat and controls the HVAC Equipment just as the Thermostat would if it were wired directly.

Additionally, the Equipment Interface has two inputs that can be connected to outputs from the HVAC Equipment that are designated to go back to the Thermostat, such as an Equipment/System Monitor (L) function. The Sure-Fi App provides troubleshooting, diagnostics information, and field upgrades.

Features

General Specifications

Operating Voltage:12 to 30VAC/DC
Operating Current (@ 24VAC):0.02A (idle), 0.26A (transmit)
Operating Power (@ 24VAC):6.3VA (peak)
Thermostat Interface relays:
  • Relay Inputs (R1 – R8): 7 to 30VAC/DC
  • Minimum input ‘ON’ threshold voltage 7VAC/DC
  • Relay outputs (OUT 1, OUT 2): 30V max
Equipment Interface relays:
  • Relay inputs (IN 1, IN 2): 7 to 30V
  • Minimum input ‘ON’ threshold voltage 7VAC/DC
  • Relay outputs R1 – R5: NO contact only 0.5A, 1.5A maximum combined. The relay output voltage is equal to the input operating voltage on the unit (the input voltage connected at the +VIN pin on the unit).
  • Relay outputs R6, R7, R8: FORM A (NO/COM) contacts: 0.5A 60V max
Range:Up to 1 mile through obstructions. Greater than 50 miles line-of-sight
Operating Temperature:-40°F to +158°F (-40°C to +70C)
Storage Temperature:-67°F to +185°F (-55°C to +85°C)
Humidity:0 to 85% non-condensing
Dimensions (Thermostat Int.) :4.45”L x 2.75”W x 0.575”H (113mm x 70mm x 15mm)
Dimensions (Equipment Int.) :4.25”L x 4.20”W x 1.30”H (108mm x 107mm x 33mm)
Thermostat Interface Mounting:Mounts to single gang box or direct mount.
Equipment Interface Mounting:DIN mount or direct mount. 35mm DIN rail (DIN46277-3)
Degree of Protection:IP20 to IEC/EN 60529

Radio Transceiver Specifications

Transmit Power:1 Watt (30dBm)
Frequency Band:902 – 928MHz
Channels:72 (Frequency hopping)
Receiver Sensitivity:-133dBm
Link Budget:163dB

Device Overview: Control Interface

Figure-2: Control Interface overview

Figure 2

Control Interface: Wire Functions & Colors

Figure-6: Control Interface wire functions and colors

NAMEWIRE COLORDESCRIPTION
R1 INWHITERELAY 1 CONTROL INPUT
R2 INYELLOWRELAY 2 CONTROL INPUT
R3 INGREENRELAY 3 CONTROL INPUT
R4 INBLUERELAY 4 CONTROL INPUT
R5 IN ORANGERELAY 5 CONTROL INPUT
R6 INSLATERELAY 6 CONTROL INPUT
R7 INVIOLETRELAY 7 CONTROL INPUT
R8 INBROWNRELAY 8 CONTROL INPUT
R9 NO BLACK/WHITERELAY 9 NO TERMINAL (RELAY COMMON CONNECTED INTERNALLY TO +VIN INPUT VOLTAGE)
R10 NOBLACK/REDRELAY 10 NO TERMINAL (RELAY COMMON CONNECTED INTERNALLY TO +VIN INPUT VOLTAGE)
-VINBLACK-VIN (INPUT POWER CAN BE CONNECTED HERE OR USING J4 SCREW TERMINAL ON BACK)
+VIN RED+VIN (INPUT POWER CAN BE CONNECTED HERE OR USING J4 SCREW TERMINAL ON BACK)

Device Overview: Equipment Interface

Figure 3: Equipment Interface overview.

Figure 3

Bottom edge connector: Equipment Interface

Figure 16: Equipment Interface Bottom Edge Connector (See Figure 2 for reference).

POSITIONNAMEDESCRIPTION
1 (left)+VIN +VIN
2-VIN-VIN
3NCNOT CONNECTED
4NCNOT CONNECTED
5+VOUTUSE FOR OUTPUT VOLTAGE FOR R8 COM, FED DIRECTLY FROM THE +VIN VOLTAGE INPUT
6R8 COMRELAY 8 COMMON CONTACT
7R8 NORELAY 8 NORMALLY-OPEN TERMINAL
8NCNOT CONNECTED
9R9 INRELAY 9 CONTROL INPUT
10 (Right)R10 INRELAY 10 CONTROL INPUT

Top Edge connector: Equipment Interface

Figure 17: Equipment Interface Top Edge Connector (See Figure 2 for reference).

POSTIONNAMEDESCRIPTION
1 (Right)+VOUTCONNECTED DIRECTLY TO THE +VIN VOLTAGE INPUT
2R7 COMRELAY 7 COMMON TERMINAL
3R7 NORELAY 7 NORMALLY-OPEN TERMINAL
4R6 COMRELAY 6 COMMON TERMINAL
5R6 NO (E) RELAY 6 NORMALLY-OPEN TERMINAL
6R5 NORELAY 5 NORMALLY-OPEN TERMINAL
7R4 NORELAY 4 NORMALLY-OPEN TERMINAL
8R3 NORELAY 3 NORMALLY-OPEN TERMINAL
9R2 NORELAY 2 NORMALLY-OPEN TERMINAL
10 (Left)R1 NORELAY 1 NORMALLY-OPEN TERMINAL

Figure-9: Connecting 24VAC: The 24VAC (R) and (C) wires are shown connected to the J4 and J5 screw terminals. NOTE: The Thermostat Interface feeds the 24VAC to the Thermostat. Do not use a jumper wire.

Figure 9aFigure 9b

Wiring Examples: Equipment Interface

Figure 14: Equipment Interface wiring example.

[CONTENT NEEDED]

Figure 14

Providing Power to the Equipment Interface:

Important

Turn off the 24VAC power before connecting to the Equipment Interface. Do not turn on the 24VAC power until all of the wiring between the Equipment Interface and the HVAC Equipment is complete.

Connect the wires for the 24VAC input power to the +VIN (R) and COM (C) terminals of the Equipment Interface (see Figures 13, 14, & 15).

<#comment>

Wiring the Equipment Interface to the HVAC Equipment:

See Figures 13, 14, & 15 for reference. The Equipment Interface has eight relay outputs and two inputs that can be used with the HVAC Equipment. Using solid wire (24 Awg to 18 Awg), wire the required connections from the 10-position terminal plug(s) to the corresponding HVAC Control board terminal.

Relay 1 through Relay 5:

Relay 1 through Relay 5 have only the NO (Normally Open) relay contact available on the terminal connector. The relay COMMON contact of Relay 1 through Relay 5 is internally connected to the +VIN (R) power input such that when the relay is energized, the +VIN (R) will then be present on the relay NO contact. This allows for simplified wiring of Relays 1 through 5.

Relay 6 through 8 (see Figure 23):

Relays 6, 7, and 8 have the NO (Normally Open) and the COMMON contacts (FORM A) available on the terminal connector. If any of these relays are to be used, the COMMON contact for the relay will have to be connected to a voltage source that is required for the device that is being controlled with the relay. A typical connection method that can be used If the voltage that is on +VIN (R) terminal is adequate for the relay control function, is to use a jumper wire to connect the +VOUT (on the right side of the top connector) to the R6 COM and/or the R7 COM to use either of those two relays. If Relay 8 is being used, a jumper wire from the +VOUT that is next to the R8 COM terminal position, can be placed between this +VOUT position to the R8 COM terminal position.

IN1 (L) and IN2:

The IN1 (L) and IN2 on the bottom terminal connector are wired to outputs from the HVAC Equipment that are normally connected back to the Thermostat, for example an Equipment/System Monitor connections.

Equipment Interface: Test (Range Test) Push Button

<#comment>

Range Test: Pressing and releasing the ‘Test’ button quickly initiates the Range Test. The Range Test feature is used to test the signal strength of the radio transceiver between the Equipment and Thermostat Interfaces. The result of the Range Test is displayed on the six blue LEDs, these are labeled ‘Signal Strength LEDS (1 – 6)’ in Figure 13. Maximum signal strength is indicated when LEDs 1 through 6 all flash ON momentarily, and minimum signal strength is indicated when only LED 1 flashes ON.

<#comment>

Thermostat Interface: Status LED (Refer to Figure 2)

Status LED: The Green Status LED is located on the side of the Thermostat Interface unit. The LED is mounted to the board and is visible through a small hole in the side of the case. The LED uses flash-codes to show system status and can be used to assist with troubleshooting.

Equipment Interface: LEDS (Refer to Figure 13)

  1. Rx LED: The Rx LED will flash once briefly when a Sure-Fi radio transmission is received.
  2. Tx LED: The Tx LED will flash once briefly upon a radio transmission.
  3. Signal Strength LEDs: These six LEDs display the received signal strength. Maximum signal strength is indicated when LEDs 1 through 6 all flash ON. Minimum signal strength is indicated when only LED 1 flashes ON.
  4. Heat (Red), Cool (Blue), and Fan (Green) LED’s: The red ‘Heat’ LED will light when the Equipment Interface R1(W,O/B) output is ON. The blue ‘Cool’ LED will light when the Equipment Interface R2(Y) output is ON. The green ‘Fan’ LED will light when the Equipment Interface R3(G) output is ON.
Note

The Red, Blue, and Green LEDs will only correspond with the Heat, Cool, and Fan functions if both the Thermostat Interface and the Equipment Interface are wired accordingly.

Equipment Interface: Antenna

The radio antenna is created using copper traces on both sides of the PC Board. Use caution when handling and mounting the unit to ensure that no damage (scratches, etc) occurs to the PC Board/Antenna. Additionally, for best performance, keep cables and wiring away from the antenna and mount the unit oriented with the antenna upwards.

Equipment Interface: Connectors

The top and bottom connectors are 10-position, 3.5mm EURO type. The mating plug is Molex pn 39500-0010. Wire Range: 16 to 30AWG. Wire strip length 0.250”. Recommended screwdriver: slotted blade 0.98” width. To install a wire, turn the screw counter-clockwise 3 or 4 turns, insert the wire and hold in place while tightening the screw. When complete, pull on the wire to ensure that it is tightened adequately.

Mounting Orientation and Guidelines

<#comment>

Thermostat Interface Unit:

The Thermostat Interface unit can be mounted to the wall behind the Thermostat in the vertical or horizontal orientation or it can be placed within the wall. The hole spacing is 3.25” which will fit a single-gang electrical box if required. The hole is sized for up to a #8 screw size.

The Equipment Interface Unit:

The Equipment Interface unit will function optimally when oriented with the Antenna positioned at top side of the unit and mounted vertically (see Figure 19). For the best RF range, route all wires and cables away from the Antenna and avoid having any wires crossing directly over the Equipment Interface unit.

There are two common methods for mounting the Equipment Interface Unit:

DIN Rail mount:

DIN rail mounting allows the unit to easily clip and unclip from the DIN rail. Attach a piece (minimum 4” length) of 35mm type DIN rail to the wall and then snap the unit to the DIN rail or slide it on from the end. The unit will snap in to place by putting the top retaining tabs on to the DIN rail first, then pressing the bottom on to the DIN rail until it snaps in to place, the bottom DIN clip may need to be pressed upward to seat into its locked position. To remove the unit from the DIN rail, use a small screwdriver, insert in to the bottom DIN rail clip and pull gently down and outward until the unit releases from the DIN rail.

Screw mount:

The DIN rail clips on the base of the enclosure case can be snapped outward to allow for screw mounting of the case. Mount using only the single bottom DIN clip and the top DIN clip that is located on the side below the 10-position connector. Do not use the DIN clip located behind the antenna. See Figures 20 – 24.

Important

If mounting the unit to metal, take note that metal shavings that are created can drop into the unit and damage the electronics. To avoid any metal shavings from dropping down in to the case, it is recommended to remove the top DIN clip completely from the base and secure it to the wall first, then slide the case on to the DIN clip. The second screw can then be secured through the bottom DIN clip without removing the clip. #8 self-drilling screws are recommended. Do not use any screw that is larger than a #8 size.

Figure 18: The two DIN Clips are shown pressed outward for direct screw mounting.

Figure 18

Figure 19: Top DIN Clip is shown removed from the base to mount the DIN clip separately.

Figure 19

Figure 20: Top DIN Clip is shown mounted first to avoid any metal shavings from dropping in to the case.

Figure 20<#comment>

Figure 21: The DIN clip on the top is shown secured with a #8 screw and the base reconnected to the DIN clip.

Figure 21

Figure 22: The DIN clip on the bottom is shown secured with the #8 screw:

Figure22

Figure 23: Equipment Interface with the relay COM of R6, R7, and R8 shown wired to +VOUT

Figure 23

Troubleshooting

If the Thermostat does not appear to be communicating with the Equipment Interface:

Range Test:

Press and release the ‘Test’ button on the Equipment Interface unit and observe the six Signal Strength LEDs. If any of blue LED 1 through LED 6 LEDs light up (flash), then the radio transmission between the two units was successful which means that the two units are powered, operating, and can transmit and receive properly. Perform the Range Test several times to ensure communications and note how many of the blues LEDs are lighting up.

Next, check the following:

  1. Check for proper power input (20 to 30VAC)
  2. Ensure that all wiring is correct
  3. Check that all wiring connections are securely connected
  4. Check that the wire insulation is stripped back far enough and is not interfering with the electrical connection in the pluggable terminal connector.
  5. Ensure that the 10-position pluggable terminal connectors are plugged in and seated down all the way.
  6. Ensure that the 10-position pluggable terminal connectors are not offset to left or to the right.

Sure-Fi App:

The Sure-Fi APP allows for firmware updates and configuration as well as for some diagnostics and troubleshooting information. The APP is continually being updated to provide for more information and features and to improve its ease of use. To download, search for ‘Sure-Fi’ and then download and install. The key features of the APP are:









FCC and Industry Canada Regulatory Statements

FCC

This device complies with part 15 of the FCC rules. Operation is subject to the following two conditions: (1) This device may not cause harmful interference, and (2) this device must accept any interference received, including interference that may cause undesired operation. Any changes or modifications not expressly approved by manufacturer could void the user’s authority to operate the equipment.



IMPORTANT! Any changes or modifications not expressly approved by the party responsible for compliance could void the user’s authority to operate this equipment.



Industry Canada

This device complies with Industry Canada license-exempt RSS standard(s). Operation is subject to the following two conditions: (1) this device may not cause interference, and (2) this device must accept any interference, including interference that may cause undesired operation of the device.



Le présent appareil est conforme aux CNR d’Industrie Canada applicables aux appareils radio exempts de licence. L’exploitation est autorisée aux deux conditions suivantes: (1) l’appareil ne doit pas produire de brouillage, et (2) l’utilisateur de l’appareil doit accepter tout brouillage radioélectrique subi, meme si le brouillage est susceptible d’en compromettre le fonctionnement.



IMPORTANT! Tous les changements ou modifications pas expressément approuvés par la partie responsable de la conformité ont pu vider l’autorité de l’utilisateur pour actioner cet équipment.



47 CFR 15.105- FCC

NOTE: This equipment has been tested and found to comply with the limits for a Class B digital device, pursuant to part 15 of the FCC Rules. These limits are designed to provide reasonable protection against harmful interference in a residential installation. This equipment generates, uses and can radiate radio frequency energy and, if not installed and used in accordance with the instructions, may cause harmful interference to radio communications. However, there is no guarantee that interference will not occur in a particular installation. If this equipment does cause harmful interference to radio or television reception, which can be determined by turning the equipment off and on, the user is encouraged to try to correct the interference by one or more of the following measures:





This Class B digital apparatus complies with Canadian ICES-003.

Cet appareil numérique de la classe B est conforme à la norme NMB-003 du Canada



FCC Radiation Exposure Statement

This equipment complies with FCC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator and your body.

Important Note:

Radiation Exposure Statement:

This equipment complies with IC radiation exposure limits set forth for an uncontrolled environment. This equipment should be installed and operated with minimum distance 20cm between the radiator and your body.



Note Importante: (Pour l’utilisation de dispositifs mobiles) Declaration d’exposition aus radiations:

Cet équipement est conforme aux limites d´exposition aux rayonnements IC établies pour un environnement non contrôlé. Cet équipment doit être installé et utilisé avec un mimimum de 20 cm de distance entre la source de rayonnement et votre corps.









Warranty

The warranty period of this product is 5 years from purchase date, beginning from first power up of the device after purchase. During this period, if the product does not operate correctly, due to a defective component, the product will be repaired or replaced at the sole discretion of Sure-Fi, Inc. This warranty does not extend to the product casing which can be damaged by conditions outside of the control of Sure-Fi, Inc.

EXCEPT AS SET FORTH ABOVE, SURE-FI, INC. MAKES NO WARRANTIES REGARDING THE GOODS, EXPRESS OR IMPLIED, INCLUDING WARRANTY OF MERCHANTABILITY OR WARRANTY OF FITNESS FOR A PARTICULAR PURPOSE. BUYER MAKES NO RELIANCE ON ANY REPRESENTATION OF SURE-FI, INC., EXPRESS OR IMPLIED, WITH REGARD TO THE GOODS AND ACCEPTS THEM “AS-IS/WHERE-IS”. SURE-FI, INC SELLS THE GOODS TO BUYER ON CONDITION THAT SURE-FI, INC. WILL HAVE NO LIABILITY OF ANY KIND AS A RESULT OF THE SALE. BUYER AGREES THAT SURE-FI, INC. SHALL HAVE NO LIABILITY FOR DAMAGES OF ANY KIND, WHETHER DIRECT, INCIDENTAL OR CONSEQUENTIAL DAMAGES, INCLUDING INJURIES TO PERSONS OR PROPERTY, TO BUYER, ITS EMPLOYEES OR AGENTS, AS A RESULT OF THE SALE. BUYER ALSO AGREES TO HOLD SURE-FI, INC. HARMLESS FROM ANY CLAIMS BUYER, OR ANY THIRD PARTY, MAY HAVE AS A RESULT OF BUYER’S USE OR DISPOSAL OF THE GOODS. BUYER HAS READ THIS DISCLAIMER AND AGREES WITH ITS TERMS IN CONSIDERATION OF RECEIVING THE GOODS.